11-14 Guidelines for Creating or Modifying Actions
LX Series Configuration Guide
X To configure a power input voltage threshold trigger
Execute the power input A|B voltage <|> <threshold_
number> [hysteresis <hysteresis_number>] command
from the Trigger-Action Command Mode to define a threshold
based off of the current voltage reading. It polls the Digital
Volt Meter (DVM) every second:
Example Trigger_TestA:0 >>power input A voltage < 48
hysteresis 1
where the input (A or B) is the input on which you want to
detect voltage with the attached device.
If the defined threshold is exceeded, the appropriate action is
executed when the rule is enabled. The action is executed
again when the voltage falls back below the threshold (plus or
minus the hysteresis) and then crosses it again. Valid
threshold values are in the range from 0.0 to 80. Valid
hysteresis values are in the range is -10.0 to 10 (note that
you can use decimals).
X To configure a power input status threshold trigger
Execute the power input A|B powered|no power command
from the Trigger-Action Command Mode to define a threshold
based off of the powered or no powered state.
Example Trigger_TestA:0 >>power input A status powered
where the input (A or B) is the input on which you want to
detect power status with the attached device.
If the defined power status changes, the appropriate action is
executed when the rule is enabled. The action is executed
again when the power status changes again.